No functions at all
|
No pump flow
|
Investigate and rectify
|
|
No pilot pressure. Pilot pressurising valve stuck / jammed open.
|
Remove and check. Piston should move freely against the spring. Clean or replace.
|
|
No power to the coils.
|
Check the voltage at the solenoid plug. Investigate and rectify.
|
|
Low voltage.
|
Check the voltage at the solenoid plug. Must be 75% minimum of the coil rating. Investigate and rectify.
|
|
One section failed – both directions
|
Damper orifice blocked. No pilot feed to the main spool.
|
Remove the manifold, examine and clean the damper orifice.
|
|
No power to the coils.
|
Check the voltage at the solenoid plug. Investigate and rectify.
|
|
Main spool stuck.
|
Remove solenoid manifold to access the main spool and check for free movement. Clean and replace.
|
|
One section failed – one direction
|
Coil open circuit.
|
Check continuity / resistance and replace if faulty. 12vDC = 6Ω +/- 10% 24vDC = 24Ω +/- 10%
|
|
Pilot cartridge spool jammed – contamination or damage.
|
Remove, check operation (audible ‘click’ when energised with spool movement). Clean / replace if faulty.
|
|
Self-operation / hesitation of manual override(s). Especially when the system is cold
|
High return line pressure – must not exceed 18 bar at maximum flow / minimum temperature conditions.
Check at Outlet cover port.
1) Inadequate hose diameter for flow / length.
2) Return line filter inadequate for flow or blocked.
3) QR connectors generating pressure.
|
1) Increase hose size.
2) Increase filter size or replace if blocked.
3) Increase QR size (or eliminate).
|
|
Operates cold, becomes intermittent with increasing temperature.
|
Low pilot pressure. Pilot pressurising valve partially jammed open or sticking.
|
Remove and check. Piston should move freely against the spring. Clean or replace.
|
|
Borderline voltage. The coil efficiency will decrease with increasing temperature.
|
Check the voltage at the solenoid plug. Must be 75% minimum of the coil rating. Investigate and rectify.
|
|
Jerky movements of actuators.
|
Intermittent loss of service port pressure due to actuator over run.
|
1) Use restrictors to maintain service port pressure.
2) Use over centre valves.
3) Increase the flow.
|
|
Partial or erratic spool / lever movement when machine is unloaded.
|
Loss of service port pressure due to low operating pressure.
|
1) Use restrictors to maintain service port pressure.
2) Increase the flow.
|